16.8.2
Functionality
GOOSESPRCV is used to receive a single point value using IEC61850 protocol via
GOOSE.
16.8.3
Function block
GOOSESPRCV
BLOCK
^SPOUT
DATAVALID
COMMVALID
TEST
IEC10000248-1-en.vsd
IEC10000248 V1 EN
Figure 341:
GOOSESPRCV function block
16.8.4
Signals
Table 560:
GOOSESPRCV Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of function
Table 561:
GOOSESPRCV Output signals
Name
Type
Description
SPOUT
BOOLEAN
Single point output
DATAVALID
BOOLEAN
Data valid for single point output
COMMVALID
BOOLEAN
Communication valid for single point output
TEST
BOOLEAN
Test output
16.8.5
Settings
Table 562:
GOOSESPRCV Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
-
-
Disabled
Operation Off/On
16.8.6
Operation principle
The DATAVALID output will be HIGH if the incoming message is with valid data.
1MRK 506 335-UUS A
Section 16
Station communication
731
Technical manual