7.12.4
Signals
Table 145:
STBPTOC (50STB) Input signals
Name
Type
Default
Description
I3P
GROUP
SIGNAL
-
Three phase group signal for current inputs
BLOCK
BOOLEAN
0
Block of function
ENABLE
BOOLEAN
0
Enable stub protection usually with open disconnect
switch (89b)
Table 146:
STBPTOC (50STB) Output signals
Name
Type
Description
TRIP
BOOLEAN
Common trip signal
PICKUP
BOOLEAN
General pickup signal
7.12.5
Settings
Table 147:
STBPTOC (50STB) Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
-
-
Disabled
Disable/Enable Operation
IPickup
1 - 2500
%IB
1
200
Pickup current level in % of IBase
Table 148:
STBPTOC (50STB) Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
GlobalBaseSel
1 - 6
-
1
1
Selection of one of the Global Base Value
groups
7.12.6
Monitored data
Table 149:
STBPTOC (50STB) Monitored data
Name
Type
Values (Range)
Unit
Description
I_A
REAL
-
A
Current in phase A
I_B
REAL
-
A
Current in phase B
I_C
REAL
-
A
Current in phase C
1MRK 506 335-UUS A
Section 7
Current protection
269
Technical manual
Содержание REL650 series
Страница 1: ...Relion 650 series Line distance protection REL650 ANSI Technical manual ...
Страница 2: ......
Страница 42: ...36 ...
Страница 48: ...42 ...
Страница 58: ...52 ...
Страница 68: ...62 ...
Страница 74: ...68 ...
Страница 194: ...188 ...
Страница 534: ...528 ...
Страница 580: ...574 ...
Страница 722: ...716 ...
Страница 792: ...786 ...
Страница 855: ...849 ...