Section 10
Secondary system supervision
10.1
Current circuit supervision CCSRDIF (87)
10.1.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Current circuit supervision
CCSRDIF
-
87
10.1.2
Functionality
Open or short circuited current transformer cores can cause unwanted operation of many
protection functions such as differential, ground-fault current and negative-sequence
current functions.
It must be remembered that a blocking of protection functions at an occurrence of open CT
circuit will mean that the situation will remain and extremely high voltages will stress the
secondary circuit.
Current circuit supervision (CCSRDIF, 87) compares the residual current from a three
phase set of current transformer cores with the neutral point current on a separate input
taken from another set of cores on the current transformer.
A detection of a difference indicates a fault in the circuit and is used as alarm or to block
protection functions expected to give inadvertent tripping.
10.1.3
Function block
ANSI08000055-1-en.vsd
CCSRDIF (87)
I3P*
BLOCK
IREF
FAIL
ALARM
ANSI08000055 V1 EN
Figure 154:
CCSRDIF (87) function block
1MRK 506 335-UUS A
Section 10
Secondary system supervision
329
Technical manual
Содержание REL650 series
Страница 1: ...Relion 650 series Line distance protection REL650 ANSI Technical manual ...
Страница 2: ......
Страница 42: ...36 ...
Страница 48: ...42 ...
Страница 58: ...52 ...
Страница 68: ...62 ...
Страница 74: ...68 ...
Страница 194: ...188 ...
Страница 534: ...528 ...
Страница 580: ...574 ...
Страница 722: ...716 ...
Страница 792: ...786 ...
Страница 855: ...849 ...