![ABB REL650 series Скачать руководство пользователя страница 770](http://html.mh-extra.com/html/abb/rel650-series/rel650-series_technical-manual_4784770.webp)
17.7.3
Settings
The function does not have any parameters available in the local HMI or PCM600.
17.8
Primary system values PRIMVAL
17.8.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Primary system values
PRIMVAL
-
-
17.8.2
Functionality
The rated system frequency and phasor rotation are set under
Main menu/
Configuration/ Power system/ Primary values/PRIMVAL
in the local HMI and
PCM600 parameter setting tree.
17.8.3
Settings
Table 590:
PRIMVAL Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Frequency
50.0 - 60.0
Hz
10.0
50.0
Rated system frequency
PhaseRotation
Normal=ABC
Inverse=ACB
-
-
Normal=ABC
System phase rotation
17.9
Signal matrix for analog inputs SMAI
17.9.1
Functionality
Signal matrix for analog inputs function (SMAI), also known as the preprocessor
function, processes the analog signals connected to it and gives information about all
aspects of the analog signals connected, like the RMS value, phase angle, frequency,
harmonic content, sequence components and so on. This information is then used by the
respective functions in ACT (for example protection, measurement or monitoring).
The SMAI function is used within PCM600 in direct relation with the Signal Matrix tool
or the Application Configuration tool.
Section 17
1MRK 506 335-UUS A
Basic IED functions
764
Technical manual
Содержание REL650 series
Страница 1: ...Relion 650 series Line distance protection REL650 ANSI Technical manual ...
Страница 2: ......
Страница 42: ...36 ...
Страница 48: ...42 ...
Страница 58: ...52 ...
Страница 68: ...62 ...
Страница 74: ...68 ...
Страница 194: ...188 ...
Страница 534: ...528 ...
Страница 580: ...574 ...
Страница 722: ...716 ...
Страница 792: ...786 ...
Страница 855: ...849 ...