The output trip signal TRIP is a three-phase trip. It can be used to command a trip to the
circuit breaker or for alarm purpose only.
BLOCK
Function Enable
TEST-ACTIVE
AND
TEST
Block BRCPTOC=Yes
OR
PU_N
AND
Unsymmetrical
Current Detection
PICKUP
IA<50%
Pickup_PH
IB<50%
Pickup_PH
IC<50%
Pickup_PH
ANSI09000158-3-en.vsd
OR
TRIP
0
0-t
ANSI09000158 V3 EN
Figure 131:
Simplified logic diagram for Broken conductor check BRCPTOC (46)
7.14.8
Technical data
Table 162:
BRCPTOC (46) technical data
Function
Range or value
Accuracy
Minimum phase current for operation
(5–100)% of
IBase
± 1.0% of I
n
Unbalance current operation
(50-90)% of maximum current
± 2.0% of I
n
Timer
(0.00-60.000) s
± 0.5% ± 25 ms
Trip time for pickup function
35 ms typically
-
Reset time for pickup function
30 ms typically
-
Critical impulse time
15 ms typically
-
Impulse margin time
10 ms typically
-
Section 7
1MRK 506 335-UUS A
Current protection
278
Technical manual