IB16FCVB function can receive remote values over IEC61850 when the operator position
input PSTO is in position remote. The block input will freeze the output at the last value.
13.9.3
Function block
IB16FCVB
BLOCK
PSTO
OUT1
OUT2
OUT3
OUT4
OUT5
OUT6
OUT7
OUT8
OUT9
OUT10
OUT11
OUT12
OUT13
OUT14
OUT15
OUT16
IEC09000399-1-en.vsd
IEC09000399 V1 EN
Figure 276:
IB16FCVB function block
13.9.4
Signals
Table 413:
IB16FCVB Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of function
PSTO
INTEGER
1
Operator place selection
Table 414:
IB16FCVB Output signals
Name
Type
Description
OUT1
BOOLEAN
Output 1
OUT2
BOOLEAN
Output 2
OUT3
BOOLEAN
Output 3
OUT4
BOOLEAN
Output 4
OUT5
BOOLEAN
Output 5
OUT6
BOOLEAN
Output 6
OUT7
BOOLEAN
Output 7
OUT8
BOOLEAN
Output 8
OUT9
BOOLEAN
Output 9
Table continues on next page
1MRK 506 335-UUS A
Section 13
Logic
567
Technical manual