![ABB REL650 series Скачать руководство пользователя страница 177](http://html.mh-extra.com/html/abb/rel650-series/rel650-series_technical-manual_4784177.webp)
6.6.4
Signals
Table 54:
PPLPHIZ Input signals
Name
Type
Default
Description
I3P
GROUP
SIGNAL
-
Three phase group signal for current inputs
V3P
GROUP
SIGNAL
-
Three phase group signal for voltage inputs
BLOCK
BOOLEAN
0
Block of function
RELAG
BOOLEAN
0
Release condition for the A to ground loop
RELBG
BOOLEAN
0
Release condition for the B to ground loop
RELCG
BOOLEAN
0
Release condition for the C to ground loop
PHSEL
INTEGER
0
Integer coded external release signal
Table 55:
PPLPHIZ Output signals
Name
Type
Description
PICKUP
BOOLEAN
Indicates start for ground fault(s), regardless of direction
ZREL
INTEGER
Integer coded output release signal
6.6.5
Settings
Table 56:
PPLPHIZ Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
OperMode
No Filter
NoPref
1231c
1321c
123a
132a
213a
231a
312a
321a
-
-
No Filter
Operating mode (c=cyclic,a=acyclic)
PU27PN
10.0 - 100.0
%VB
1.0
70.0
Operate value of phase undervoltage in % of
VBase
PU27PP
10.0 - 100.0
%VB
1.0
50.0
Operate value of line to line undervoltage in %
of VBase
3V0PU
5.0 - 300.0
%VB
1.0
20.0
Operate value of residual voltage in % of
VBase
Pickup_N
10 - 200
%IB
1
20
Operate value of residual current in % of IBase
tVN
0.000 - 60.000
s
0.001
0.100
Pickup delay for residual voltage
tOffVN
0.000 - 60.000
s
0.001
0.100
Dropoff delay for residual voltage
tIN
0.000 - 60.000
s
0.001
0.150
Pickup delay for residual current
1MRK 506 335-UUS A
Section 6
Impedance protection
171
Technical manual
Содержание REL650 series
Страница 1: ...Relion 650 series Line distance protection REL650 ANSI Technical manual ...
Страница 2: ......
Страница 42: ...36 ...
Страница 48: ...42 ...
Страница 58: ...52 ...
Страница 68: ...62 ...
Страница 74: ...68 ...
Страница 194: ...188 ...
Страница 534: ...528 ...
Страница 580: ...574 ...
Страница 722: ...716 ...
Страница 792: ...786 ...
Страница 855: ...849 ...