11.8.3
Function block
DPGGIO
OPEN
CLOSE
VALID
POSITION
IEC09000075_1_en.vsd
IEC09000075 V1 EN
Figure 221:
DPGGIO function block
11.8.4
Signals
Table 309:
DPGGIO Input signals
Name
Type
Default
Description
OPEN
BOOLEAN
0
Open indication
CLOSE
BOOLEAN
0
Close indication
VALID
BOOLEAN
0
Valid indication
Table 310:
DPGGIO Output signals
Name
Type
Description
POSITION
INTEGER
Double point indication
11.8.5
Settings
The function does not have any parameters available in Local HMI or Protection and
Control IED Manager (PCM600).
11.8.6
Operation principle
Upon receiving the input signals, the IEC 61850 generic communication I/O functions
(DPGGIO) function block will send the signals over IEC 61850-8-1 to the equipment or
system that requests these signals. To be able to get the signals, PCM600 must be used to
define which function block in which equipment or system should receive this
information.