Table 393:
AND Output signals
Name
Type
Description
OUT
BOOLEAN
Output signal
NOUT
BOOLEAN
Inverted output signal
Settings
The function does not have any parameters available in Local HMI or Protection and
Control IED Manager (PCM600).
13.4.1.10
Set-reset memory function block SRMEMORY
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Set-reset memory function block
SRMEMORY
-
-
Functionality
The Set-Reset function SRMEMORY is a flip-flop with memory that can set or reset an
output from two inputs respectively. Each SRMEMORY function block has two outputs,
where one is inverted. The memory setting controls if the flip-flop after a power
interruption will return the state it had before or if it will be reset. For a Set-Reset flip-flop,
SET input has higher priority over RESET input.
Table 394:
Truth table for the Set-Reset (SRMEMORY) function block
SET
RESET
OUT
NOUT
1
0
1
0
0
1
0
1
1
1
1
0
0
0
0
1
Function block
SRMEMORY
SET
RESET
OUT
NOUT
IEC09000293-1-en.vsd
IEC09000293 V1 EN
Figure 270:
SRMEMORY function block
Section 13
1MRK 506 335-UUS A
Logic
552
Technical manual
Содержание REL650 series
Страница 1: ...Relion 650 series Line distance protection REL650 ANSI Technical manual ...
Страница 2: ......
Страница 42: ...36 ...
Страница 48: ...42 ...
Страница 58: ...52 ...
Страница 68: ...62 ...
Страница 74: ...68 ...
Страница 194: ...188 ...
Страница 534: ...528 ...
Страница 580: ...574 ...
Страница 722: ...716 ...
Страница 792: ...786 ...
Страница 855: ...849 ...