Name
Values (Range)
Unit
Step
Default
Description
Power2
0.0 - 500.0
%
0.1
1.0
Power setting for stage 2 in % of calculated
power base value
Angle2
-180.0 - 180.0
Deg
0.1
0.0
Characteristic angle for stage 2
TripDelay2
0.010 - 6000.000
s
0.001
1.000
Trip delay for stage 2
Table 172:
GUPPDUP (37) Group settings (advanced)
Name
Values (Range)
Unit
Step
Default
Description
TD
0.00 - 0.99
-
0.01
0.00
Low pass filter coefficient for power
measurement, V and I
Table 173:
GUPPDUP (37) Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
GlobalBaseSel
1 - 6
-
1
1
Selection of one of the Global Base Value
groups
Mode
A, B, C
Arone
Pos Seq
AB
BC
CA
A
B
C
-
-
Pos Seq
Mode of measurement for current and voltage
7.15.3.5
Monitored data
Table 174:
GUPPDUP (37) Monitored data
Name
Type
Values (Range)
Unit
Description
P
REAL
-
MW
Active Power
PPERCENT
REAL
-
%
Active power in % of
calculated power base value
Q
REAL
-
MVAr
Reactive power
QPERCENT
REAL
-
%
Reactive power in % of
calculated power base value
7.15.4
Operation principle
A simplified scheme showing the principle of the power protection function is shown in
figure
. The function has two stages with individual settings.
Section 7
1MRK 506 335-UUS A
Current protection
284
Technical manual
Содержание REL650 series
Страница 1: ...Relion 650 series Line distance protection REL650 ANSI Technical manual ...
Страница 2: ......
Страница 42: ...36 ...
Страница 48: ...42 ...
Страница 58: ...52 ...
Страница 68: ...62 ...
Страница 74: ...68 ...
Страница 194: ...188 ...
Страница 534: ...528 ...
Страница 580: ...574 ...
Страница 722: ...716 ...
Страница 792: ...786 ...
Страница 855: ...849 ...