Figure 167:
Logic diagram for the voltage selection function of a single circuit breaker with double busbars
11.1.7.8
Voltage selection for a breaker-and-a-half circuit breaker arrangement
Note that with breaker-and-a-half schemes three Synchronism check functions must be
used for the complete diameter. Below, the scheme for one Bus breaker and the Tie
breaker is described.
This voltage selection function uses the binary inputs from the disconnectors and circuit
breakers auxiliary contacts to select the right voltage for the SESRSYN (Synchronism,
Synchronizing and Energizing check) function. For the bus circuit breaker one side of the
circuit breaker is connected to the busbar and the other side is connected either to line 1,
line 2 or the other busbar depending on the best selection of voltage circuit.
Inputs LINE1_OP-LINE1_CL, BUS1_OP-BUS1_CL, BUS2_OP-BUS2_CL,
LINE2_OP-LINE2_CL are inputs for the position of the Line disconnectors respectively
the Bus and Tie breakers. The outputs L1SEL, L2SEL and B2SEL will give indication of
1MRK 506 335-UUS A
Section 11
Control
359
Technical manual
Содержание REL650 series
Страница 1: ...Relion 650 series Line distance protection REL650 ANSI Technical manual ...
Страница 2: ......
Страница 42: ...36 ...
Страница 48: ...42 ...
Страница 58: ...52 ...
Страница 68: ...62 ...
Страница 74: ...68 ...
Страница 194: ...188 ...
Страница 534: ...528 ...
Страница 580: ...574 ...
Страница 722: ...716 ...
Страница 792: ...786 ...
Страница 855: ...849 ...