Name
Values (Range)
Unit
Step
Default
Description
UVPickup
1 - 100
%VB
1
70
Voltage level for detection of dead line in % of
VBase
tDuration
0.000 - 60.000
s
0.001
0.020
Time delay for UI detection
tSOTF
0.000 - 60.000
s
0.001
1.000
Drop off delay time of switch onto fault function
tDLD
0.000 - 60.000
s
0.001
0.200
Delay time for activation of dead line detection
Table 69:
ZCVPSOF Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
GlobalBaseSel
1 - 6
-
1
1
Selection of one of the Global Base Value
groups
6.8.6
Operation principle
Automatic switch onto fault logic, voltage and current based function (ZCVPSOF) can be
activated externally by Breaker Closed Input or internally (automatically) by using VI
Level Based Logic see figure
.
The activation from the Dead line detection function is released if the internal signal
deadLine from the VILevel function is activated at the same time as the input ZACC is not
activated during at least for a duration
tDLD
and the setting parameter
AutoInit
is set to
Enabled
.
When the setting
AutoInit
is
Disabled
, the function is activated by an external binary input
BC. To get a trip one of the following operation modes must also be selected by the
parameter
Mode
:
Mode = Impedance
; trip is released if the input ZACC is activated (normal connected to
non directional distance protection zone).
Mode = VILevel
; trip is released if VILevel detector is activated.
Mode = VILvl&Imp
; trip is initiated based on impedance measured criteria or VILevel
detection.
The internal signal deadLine from the VILevel detector is activated if all three phase
currents and voltages are below the setting
IPhPickup
and
UVPickup
.
VI Level based measurement detects the switch onto fault condition even though the
voltage is very low. The logic is based on current and voltage levels. The internal signal
SOTF VILevel is activated if a phase voltage is below the setting
UVPickup
and
corresponding phase current is above the setting
IPhPickup
longer than the time
tDuration
.
1MRK 506 335-UUS A
Section 6
Impedance protection
185
Technical manual
Содержание REL650 series
Страница 1: ...Relion 650 series Line distance protection REL650 ANSI Technical manual ...
Страница 2: ......
Страница 42: ...36 ...
Страница 48: ...42 ...
Страница 58: ...52 ...
Страница 68: ...62 ...
Страница 74: ...68 ...
Страница 194: ...188 ...
Страница 534: ...528 ...
Страница 580: ...574 ...
Страница 722: ...716 ...
Страница 792: ...786 ...
Страница 855: ...849 ...