Table 240:
SESRSYN (25) Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
GblBaseSelBus
1 - 6
-
1
1
Selection of one of the Global Base Value
groups, Bus
GblBaseSelLine
1 - 6
-
1
1
Selection of one of the Global Base Value
groups, Line
SelPhaseBus1
Phase L1
Phase L2
Phase L3
Phase L1L2
Phase L2L3
Phase L3L1
Positive sequence
-
-
Phase L1
Select phase for busbar1
SelPhaseBus2
Phase L1
Phase L2
Phase L3
Phase L1L2
Phase L2L3
Phase L3L1
Positive sequence
-
-
Phase L1
Select phase for busbar2
SelPhaseLine1
Phase L1
Phase L2
Phase L3
Phase L1L2
Phase L2L3
Phase L3L1
Positive sequence
-
-
Phase L1
Select phase for line1
SelPhaseLine2
Phase L1
Phase L2
Phase L3
Phase L1L2
Phase L2L3
Phase L3L1
Positive sequence
-
-
Phase L1
Select phase for line2
11.1.6
Monitored data
Table 241:
SESRSYN (25) Monitored data
Name
Type
Values (Range)
Unit
Description
VDIFFME
REAL
-
-
Calculated difference of
voltage in p.u of set voltage
base value
FRDIFFME
REAL
-
Hz
Calculated difference of
frequency
PHDIFFME
REAL
-
deg
Calculated difference of phase
angle
Vbus
REAL
-
kV
Bus voltage
VLine
REAL
-
kV
Line voltage
Section 11
1MRK 506 335-UUS A
Control
352
Technical manual
Содержание REL650 series
Страница 1: ...Relion 650 series Line distance protection REL650 ANSI Technical manual ...
Страница 2: ......
Страница 42: ...36 ...
Страница 48: ...42 ...
Страница 58: ...52 ...
Страница 68: ...62 ...
Страница 74: ...68 ...
Страница 194: ...188 ...
Страница 534: ...528 ...
Страница 580: ...574 ...
Страница 722: ...716 ...
Страница 792: ...786 ...
Страница 855: ...849 ...