6.8.3
Function block
ANSI09000057-1-en.vsd
ZCVPSOF
I3P*
V3P*
BLOCK
BC
ZACC
TRIP
ANSI09000057 V1 EN
Figure 86:
ZCVPSOF Function block
6.8.4
Signals
Table 66:
ZCVPSOF Input signals
Name
Type
Default
Description
I3P
GROUP
SIGNAL
-
Three phase group signal for current inputs
V3P
GROUP
SIGNAL
-
Three phase group signal for voltage inputs
BLOCK
BOOLEAN
0
Block of function
BC
BOOLEAN
0
External enabling of SOTF
ZACC
BOOLEAN
0
Distance zone to be accelerated by SOTF
Table 67:
ZCVPSOF Output signals
Name
Type
Description
TRIP
BOOLEAN
Trip by pilot communication scheme logic
6.8.5
Settings
Table 68:
ZCVPSOF Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
-
-
Enabled
Operation Disable / Enable
Mode
Impedance
VILevel
VILvl&Imp
-
-
VILevel
Mode of operation of SOTF Function
AutoInit
Disabled
Enabled
-
-
Disabled
Automatic switch onto fault initialization
IphPickup
1 - 100
%IB
1
20
Current level for detection of dead line in % of
IBase
Table continues on next page
Section 6
1MRK 506 335-UUS A
Impedance protection
184
Technical manual
Содержание REL650 series
Страница 1: ...Relion 650 series Line distance protection REL650 ANSI Technical manual ...
Страница 2: ......
Страница 42: ...36 ...
Страница 48: ...42 ...
Страница 58: ...52 ...
Страница 68: ...62 ...
Страница 74: ...68 ...
Страница 194: ...188 ...
Страница 534: ...528 ...
Страница 580: ...574 ...
Страница 722: ...716 ...
Страница 792: ...786 ...
Страница 855: ...849 ...