Table 132:
CCRBRF (50BF) Output signals
Name
Type
Description
TRBU
BOOLEAN
Back-up trip by breaker failure protection function
TRRET
BOOLEAN
Retrip by breaker failure protection function
7.10.5
Settings
Table 133:
CCRBRF (50BF) Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
-
-
Disabled
Disable/Enable Operation
FunctionMode
Current
Contact
Current&Contact
-
-
Current
Detection principle for back-up trip
BuTripMode
2 out of 4
1 out of 3
1 out of 4
-
-
1 out of 3
Back-up trip mode
RetripMode
Retrip Off
CB Pos Check
No CBPos Check
-
-
Retrip Off
Operation mode of re-trip logic
Pickup_PH
5 - 200
%IB
1
10
Phase current pickup in % of IBase
Pickup_N
2 - 200
%IB
1
10
Operate residual current level in % of IBase
t1
0.000 - 60.000
s
0.001
0.000
Time delay of re-trip
t2
0.000 - 60.000
s
0.001
0.150
Time delay of back-up trip
Table 134:
CCRBRF (50BF) Group settings (advanced)
Name
Values (Range)
Unit
Step
Default
Description
Pickup_BlkCont
5 - 200
%IB
1
20
Current for blocking of 52a operation in % of
Ibase
Table 135:
CCRBRF (50BF) Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
GlobalBaseSel
1 - 6
-
1
1
Selection of one of the Global Base Value
groups
Section 7
1MRK 506 335-UUS A
Current protection
258
Technical manual
Содержание REL650 series
Страница 1: ...Relion 650 series Line distance protection REL650 ANSI Technical manual ...
Страница 2: ......
Страница 42: ...36 ...
Страница 48: ...42 ...
Страница 58: ...52 ...
Страница 68: ...62 ...
Страница 74: ...68 ...
Страница 194: ...188 ...
Страница 534: ...528 ...
Страница 580: ...574 ...
Страница 722: ...716 ...
Страница 792: ...786 ...
Страница 855: ...849 ...