have corresponding primary quantity, the 1:1 ratio shall be set for the used analogue
inputs on the IED, For example, HZPDIF.
•
Parameter IBase used by the tested function is set equal to the rated CT primary
current.
•
Parameter UBase used by the tested function is set equal to the rated primary phase-
to-phase voltage.
•
Parameter SBase used by the tested function is set equal to sqrt(3)* IBase* UBase for
three-phase power system.
3.4
Settings
Dependent on ordered IED type.
Table 1:
AISVBAS Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
PhaseAngleRef
TRM - Channel 1
TRM - Channel 2
TRM - Channel 3
TRM - Channel 4
TRM - Channel 5
TRM - Channel 6
TRM - Channel 7
TRM - Channel 8
TRM - Channel 9
TRM - Channel 10
AIM - Channel 1
AIM - Channel 2
AIM - Channel 3
AIM - Channel 4
AIM - Channel 5
AIM - Channel 6
AIM - Channel 7
AIM - Channel 8
AIM - Channel 9
AIM - Channel 10
-
-
TRM - Channel 1
Reference channel for phase angle
presentation
Table 2:
TRM_6I_4U Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
CTStarPoint1
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec1
0.1 - 10.0
A
0.1
1
Rated CT secondary current
CTprim1
1 - 99999
A
1
1000
Rated CT primary current
CTStarPoint2
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec2
0.1 - 10.0
A
0.1
1.0
Rated CT secondary current
Table continues on next page
1MRK 506 335-UUS A
Section 3
Analog inputs
55
Technical manual
Содержание REL650 series
Страница 1: ...Relion 650 series Line distance protection REL650 ANSI Technical manual ...
Страница 2: ......
Страница 42: ...36 ...
Страница 48: ...42 ...
Страница 58: ...52 ...
Страница 68: ...62 ...
Страница 74: ...68 ...
Страница 194: ...188 ...
Страница 534: ...528 ...
Страница 580: ...574 ...
Страница 722: ...716 ...
Страница 792: ...786 ...
Страница 855: ...849 ...