14.1.4.4
Settings
Table 432:
VMMXU Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
-
-
Disabled
Operation Disable / Enable
GlobalBaseSel
1 - 6
-
1
1
Selection of one of the Global Base Value
groups
VLDbRepInt
1 - 300
Type
1
10
Cycl: Report interval (s), Db: In % of range, Int
Db: In %s
VLMax
0 - 4000000
V
1
170000
Maximum value
VLRepTyp
Cyclic
Dead band
Int deadband
-
-
Dead band
Reporting type
VLAngDbRepInt
1 - 300
Type
1
10
Cycl: Report interval (s), Db: In % of range, Int
Db: In %s
Table 433:
VMMXU Non group settings (advanced)
Name
Values (Range)
Unit
Step
Default
Description
VLZeroDB
0 - 100000
m%
1
500
Zero point clamping
VLHiHilLim
0 - 4000000
V
1
160000
High High limit (physical value)
VLHiLim
0 - 4000000
V
1
150000
High limit (physical value)
VLLowLim
0 - 4000000
V
1
125000
Low limit (physical value)
VLowLowLim
0 - 4000000
V
1
115000
Low Low limit (physical value)
VLMin
0 - 4000000
V
1
0
Minimum value
VLLimHys
0.000 - 100.000
V
0.001
5.000
Hysteresis value in % of range and is common
for all limits
14.1.4.5
Monitored data
Table 434:
VMMXU Monitored data
Name
Type
Values (Range)
Unit
Description
V_AB
REAL
-
kV
V_AB Amplitude
VAB_ANGL
REAL
-
deg
VAB Angle
V_BC
REAL
-
kV
V_BC Amplitude
VBC_ANGL
REAL
-
deg
VBC Angle
V_CA
REAL
-
kV
V_CA Amplitude
VCA_ANGL
REAL
-
deg
VCA Angle
Section 14
1MRK 506 335-UUS A
Monitoring
586
Technical manual
Содержание REL650 series
Страница 1: ...Relion 650 series Line distance protection REL650 ANSI Technical manual ...
Страница 2: ......
Страница 42: ...36 ...
Страница 48: ...42 ...
Страница 58: ...52 ...
Страница 68: ...62 ...
Страница 74: ...68 ...
Страница 194: ...188 ...
Страница 534: ...528 ...
Страница 580: ...574 ...
Страница 722: ...716 ...
Страница 792: ...786 ...
Страница 855: ...849 ...