Figure 83:
Operating characteristic for ZMRPSB (68) function (setting parameters in
italic)
The impedance measurement within ZMRPSB (68) function is performed by solving
equation
(Typical equations are for phase A, similar equations are
applicable for phases B and C).
Re
A
A
V
Rset
I
æ
ö
£
ç
÷
è
ø
EQUATION1557 V1 EN
(Equation 37)
Im
A
A
V
Xset
I
æ
ö
£
ç
÷
è
ø
EQUATION1558 V1 EN
(Equation 38)
The R
set
and X
set
are R and X boundaries.
Section 6
1MRK 506 335-UUS A
Impedance protection
178
Technical manual