Input, Output and LED Settings
Parameter
Description
Setting range
Default
Menu path
Inverting 1
Inverting the input
signals.
inactive,
active
inactive
[Device Para
/Digital Inputs
/DI Slot X1
/Group 1]
Debouncing time 1
A change of the state of a
digital input will only be
recognized after the
debouncing time has
expired (become
effective). Thus,
transient signals will not
be misinterpreted.
no debouncing time,
20 ms,
50 ms,
100 ms
no debouncing time
[Device Para
/Digital Inputs
/DI Slot X1
/Group 1]
Nom voltage
Nominal voltage of the
digital inputs
24 V DC,
48 V DC,
60 V DC,
110 V DC,
230 V DC,
110 V AC,
230 V AC
24 V DC
[Device Para
/Digital Inputs
/DI Slot X1
/Group 2]
Inverting 2
Inverting the input
signals.
inactive,
active
inactive
[Device Para
/Digital Inputs
/DI Slot X1
/Group 2]
Debouncing time 2
A change of the state of a
digital input will only be
recognized after the
debouncing time has
expired (become
effective). Thus,
transient signals will not
be misinterpreted.
no debouncing time,
20 ms,
50 ms,
100 ms
no debouncing time
[Device Para
/Digital Inputs
/DI Slot X1
/Group 2]
Nom voltage
Nominal voltage of the
digital inputs
24 V DC,
48 V DC,
60 V DC,
110 V DC,
230 V DC,
110 V AC,
230 V AC
24 V DC
[Device Para
/Digital Inputs
/DI Slot X1
/Group 3]
Inverting 3
Inverting the input
signals.
inactive,
active
inactive
[Device Para
/Digital Inputs
/DI Slot X1
/Group 3]
EN MRM4 01/11
Page 59
Summary of Contents for MRM4
Page 1: ...MRM4 HighPROTEC Motor Protection Device Manual DOK HB MRM4E...
Page 3: ...Order Code EN MRM4 01 11 Page 3...
Page 18: ...Important Definitions Page 18 EN MRM4 01 11 41 SG Prot ON 42 SG ON Cmd SG Prot ON SG ON Cmd...
Page 115: ...Navigation Operation Navigation Operation EN MRM4 01 11 Page 115 1 2 3 5 7 6 8 10 9...
Page 162: ...Recorder Name Description I 2 TripCmd Signal Trip Command Page 162 EN MRM4 01 11...