Recorder
Parameter
Description
Setting range
Default
Menu path
Start: 6
Start recording if the
assigned signal is true.
1..n, Assignment List
-.-
[Device Para
/Recorders
/Disturb rec]
Start: 7
Start recording if the
assigned signal is true.
1..n, Assignment List
-.-
[Device Para
/Recorders
/Disturb rec]
Start: 8
Start recording if the
assigned signal is true.
1..n, Assignment List
-.-
[Device Para
/Recorders
/Disturb rec]
Auto overwriting
If there is no more free
memory capacity left, the
oldest file will be
overwritten.
inactive,
active
active
[Device Para
/Recorders
/Disturb rec]
Post-trigger time
The post trigger time is
settable up to a
maximum of 50% of the
Maximum file size
setting. The post-trigger
will be the remaining time
of the "Max file size" but
at maximum "Post-trigger
time".
0 - 50%
20%
[Device Para
/Recorders
/Disturb rec]
Pre-trigger time
The pre-trigger time is
settable up to a
maximum of 50% of the
Maximum file size
setting.
0 - 50%
20%
[Device Para
/Recorders
/Disturb rec]
Max file size
The maximum storage
capacity per record is 10
seconds, including pre-
trigger and post-trigger
time. The disturbance
recorder has a total
storage capacity of 120
seconds.
0.1 - 10.0s
2s
[Device Para
/Recorders
/Disturb rec]
Disturbance Recorder Input States
Name
Description
Assignment via
Start1-I
State of the module input:: Trigger event /
start recording if:
[Device Para
/Recorders
/Disturb rec]
Start2-I
State of the module input:: Trigger event /
start recording if:
[Device Para
/Recorders
/Disturb rec]
EN MRM4 01/11
Page 157
Summary of Contents for MRM4
Page 1: ...MRM4 HighPROTEC Motor Protection Device Manual DOK HB MRM4E...
Page 3: ...Order Code EN MRM4 01 11 Page 3...
Page 18: ...Important Definitions Page 18 EN MRM4 01 11 41 SG Prot ON 42 SG ON Cmd SG Prot ON SG ON Cmd...
Page 115: ...Navigation Operation Navigation Operation EN MRM4 01 11 Page 115 1 2 3 5 7 6 8 10 9...
Page 162: ...Recorder Name Description I 2 TripCmd Signal Trip Command Page 162 EN MRM4 01 11...