Protective Elements
Parameter
Description
Setting range
Default
Menu path
Char
Characteristic
DEFT,
IEC NINV,
IEC VINV,
IEC EINV,
IEC LINV,
ANSI MINV,
ANSI VINV,
ANSI EINV,
Therm Flat,
IT,
I2T,
I4T
DEFT
[Protection Para
/<n>
/I-Prot
/IG[1]]
t
Tripping delay
Only available if:
Characteristic = DEFT
0.00 - 300.00s
IG[1]: 0.50s
1.00s
1.00s
1.00s
1.00s
IG[2]: 0.00s
IG[3]: 0.00s
IG[4]: 0.00s
[Protection Para
/<n>
/I-Prot
/IG[1]]
t-char
Time multiplier/tripping
characteristic factor. The
setting range depends on
the selected tripping
curve.
Only available if:
Characteristic = INV Or
Characteristic = Therm
Flat Or Characteristic =
IT Or Characteristic =
I2T Or Characteristic =
I4T.
0.02 - 20.00
1
[Protection Para
/<n>
/I-Prot
/IG[1]]
Reset Mode
Reset Mode
Only available if:
Characteristic = INV Or
Characteristic = Therm
Flat Or Characteristic =
IT Or Characteristic =
I2T Or Characteristic =
I4T.
instantaneous,
t-delay,
calculated
instantaneous
[Protection Para
/<n>
/I-Prot
/IG[1]]
Page 340
EN MRM4 01/11
Summary of Contents for MRM4
Page 1: ...MRM4 HighPROTEC Motor Protection Device Manual DOK HB MRM4E...
Page 3: ...Order Code EN MRM4 01 11 Page 3...
Page 18: ...Important Definitions Page 18 EN MRM4 01 11 41 SG Prot ON 42 SG ON Cmd SG Prot ON SG ON Cmd...
Page 115: ...Navigation Operation Navigation Operation EN MRM4 01 11 Page 115 1 2 3 5 7 6 8 10 9...
Page 162: ...Recorder Name Description I 2 TripCmd Signal Trip Command Page 162 EN MRM4 01 11...