Input, Output and LED Settings
Parameter
Description
Setting range
Default
Menu path
Inverting 6
Inverting of the state of
the assigned signal.
inactive,
active
inactive
[Device Para
/Binary Outputs
/BO-5 X2
/BO 3]
Assignment 7
Assignment
1..n, Assignment List
-.-
[Device Para
/Binary Outputs
/BO-5 X2
/BO 3]
Inverting 7
Inverting of the state of
the assigned signal.
inactive,
active
inactive
[Device Para
/Binary Outputs
/BO-5 X2
/BO 3]
t-hold
To clearly identify the
state transition of a
binary output relay, the
"new state" is being hold,
at least for the duration of
the hold time.
0.00 - 300.00s
0.00s
[Device Para
/Binary Outputs
/BO-5 X2
/BO 4]
t-Off Delay
Switch Off Delay
0.00 - 300.00s
0.00s
[Device Para
/Binary Outputs
/BO-5 X2
/BO 4]
Latched
Defines whether the
Relay Output will be
latched when it picks up.
inactive,
active
inactive
[Device Para
/Binary Outputs
/BO-5 X2
/BO 4]
Acknowledgement
Acknowledgement Signal
- An acknowledgement
signal (that
acknowledges the
corresponding binary
output relay) can be
assigned to each output
relay. The
acknowledgement-signal
is only effective if the
parameter "Latched" is
set to active.
Only available if: Latched
= active
1..n, Assignment List
-.-
[Device Para
/Binary Outputs
/BO-5 X2
/BO 4]
Inverting
Inverting of the Binary
Output Relay.
inactive,
active
inactive
[Device Para
/Binary Outputs
/BO-5 X2
/BO 4]
EN MRM4 01/11
Page 75
Summary of Contents for MRM4
Page 1: ...MRM4 HighPROTEC Motor Protection Device Manual DOK HB MRM4E...
Page 3: ...Order Code EN MRM4 01 11 Page 3...
Page 18: ...Important Definitions Page 18 EN MRM4 01 11 41 SG Prot ON 42 SG ON Cmd SG Prot ON SG ON Cmd...
Page 115: ...Navigation Operation Navigation Operation EN MRM4 01 11 Page 115 1 2 3 5 7 6 8 10 9...
Page 162: ...Recorder Name Description I 2 TripCmd Signal Trip Command Page 162 EN MRM4 01 11...