Protective Elements
Parameter
Description
Setting range
Default
Menu path
TRNC
Motor start transitions
current level in Ib%
Only available if: TRN
Criteria = TRN T and I
Or TRN Criteria = TRN I.
0.10 - 3.00Ib
1.30Ib
[Protection Para
/Global Prot Para
/MStart
/Start Control]
NOCS
Number of cold starts
limit
1 - 5
1
[Protection Para
/Global Prot Para
/MStart
/Start Control]
TBS Fc
Time Between Starts on/
off
inactive,
active
inactive
[Protection Para
/Global Prot Para
/MStart
/Start Control]
TBS Timer
Time Between Starts
Limit
Only available if: TBS Fc
= active
1 - 240min
60min
[Protection Para
/Global Prot Para
/MStart
/Start Control]
SPH Fc
Starts Per Hour
inactive,
active
inactive
[Protection Para
/Global Prot Para
/MStart
/Start Control]
SPH
SPH
Only available if: SPH Fc
= active
1 - 10
1
[Protection Para
/Global Prot Para
/MStart
/Start Control]
INSQReportFrom
INcomplete SeQuence
report time starting point
inactive,
InSq Start2Run,
InSq Stop2Start
inactive
[Protection Para
/Global Prot Para
/MStart
/Start Control]
INSQReportTime
INSQ Report back time
Only available if:
INSQReportFrom =
active
1 - 240s
1s
[Protection Para
/Global Prot Para
/MStart
/Start Control]
LAT Fc
Long Time Acceleration
Timer
inactive,
active
inactive
[Protection Para
/Global Prot Para
/MStart
/Start Control]
EN MRM4 01/11
Page 275
Summary of Contents for MRM4
Page 1: ...MRM4 HighPROTEC Motor Protection Device Manual DOK HB MRM4E...
Page 3: ...Order Code EN MRM4 01 11 Page 3...
Page 18: ...Important Definitions Page 18 EN MRM4 01 11 41 SG Prot ON 42 SG ON Cmd SG Prot ON SG ON Cmd...
Page 115: ...Navigation Operation Navigation Operation EN MRM4 01 11 Page 115 1 2 3 5 7 6 8 10 9...
Page 162: ...Recorder Name Description I 2 TripCmd Signal Trip Command Page 162 EN MRM4 01 11...