Protective Elements
Parameter
Description
Setting range
Default
Menu path
Use RTD values
Take RTD values into
account for the
calculation of the
Thermal Model __
inactive,
active
inactive
[Protection Para
/Global Prot Para
/I-Prot
/ThR]
K2
This value represents the
negative sequence
current weighting factor
of the motor.
0.10 - 10.00
6.01
[Protection Para
/Global Prot Para
/I-Prot
/ThR]
τ-cool
Cooling time constant
5 - 240
60
[Protection Para
/Global Prot Para
/I-Prot
/ThR]
Setting Group Parameters of the Thermal Model
Parameter
Description
Setting range
Default
Menu path
Function
Permanent activation or
deactivation of
module/stage.
inactive,
active
active
[Protection Para
/<n>
/I-Prot
/ThR]
ExBlo Fc
Activate (allow) or
inactivate (disallow)
blocking of the
module/stage. This
parameter is only
effective if a signal is
assigned to the
corresponding global
protection parameter. If
the signal becomes true,
those modules/stages
are blocked that are
parametrized "ExBlo
Fc=active".
inactive,
active
inactive
[Protection Para
/<n>
/I-Prot
/ThR]
Blo TripCmd
Permanent blocking of
the Trip Command of the
module/stage.
inactive,
active
inactive
[Protection Para
/<n>
/I-Prot
/ThR]
EN MRM4 01/11
Page 389
Summary of Contents for MRM4
Page 1: ...MRM4 HighPROTEC Motor Protection Device Manual DOK HB MRM4E...
Page 3: ...Order Code EN MRM4 01 11 Page 3...
Page 18: ...Important Definitions Page 18 EN MRM4 01 11 41 SG Prot ON 42 SG ON Cmd SG Prot ON SG ON Cmd...
Page 115: ...Navigation Operation Navigation Operation EN MRM4 01 11 Page 115 1 2 3 5 7 6 8 10 9...
Page 162: ...Recorder Name Description I 2 TripCmd Signal Trip Command Page 162 EN MRM4 01 11...