Trip and Breaker Management
Trip and Breaker Management
CB Manager (TripControl)
CB
The tripping commands of all protection modules are combined in module
»TripLogic«
by an OR logic. The
command for tripping can come from each of the protection modules, but the actual tripping command to the CB
is only given by the module
»TripLogic«
.
In addition to that you can set within this module the minimum hold time of the tripping command and define
whether the tripping command is latched or not.
EN MRM4 01/11
Page 251