Protective Elements
Parameter
Description
Setting range
Default
Menu path
Windg 2 t-Delay
Winding 2 If this time is
expired a Temperature
Alarm will be generated.
Only available if: Device
planning: Alarm Function
= use.
0 - 360min
1min
[Protection Para
/<n>
/Temp-Prot
/RTD
/Windg 2]
Windg 2 Trip
Winding 2 Threshold for
Temperature Trip
Only available if: Device
planning: Trip Function =
use
0 - 200°C
100°C
[Protection Para
/<n>
/Temp-Prot
/RTD
/Windg 2]
Windg 3 Alarm Function
Winding 3 Alarm
Function
inactive,
active
active
[Protection Para
/<n>
/Temp-Prot
/RTD
/Windg 3]
Windg 3 Trip Function
Winding 3 Trip Function
inactive,
active
active
[Protection Para
/<n>
/Temp-Prot
/RTD
/Windg 3]
Windg 3 Alarm
Winding 3 Threshold for
Temperature Alarm
Only available if: Device
planning: Alarm Function
= use.
0 - 200°C
80°C
[Protection Para
/<n>
/Temp-Prot
/RTD
/Windg 3]
Windg 3 t-Delay
Winding 3 If this time is
expired a Temperature
Alarm will be generated.
Only available if: Device
planning: Alarm Function
= use.
0 - 360min
1 min
[Protection Para
/<n>
/Temp-Prot
/RTD
/Windg 3]
Windg 3 Trip
Winding 3 Threshold for
Temperature Trip
Only available if: Device
planning: Trip Function =
use.
0 - 200°C
100°C
[Protection Para
/<n>
/Temp-Prot
/RTD
/Windg 3]
EN MRM4 01/11
Page 365
Summary of Contents for MRM4
Page 1: ...MRM4 HighPROTEC Motor Protection Device Manual DOK HB MRM4E...
Page 3: ...Order Code EN MRM4 01 11 Page 3...
Page 18: ...Important Definitions Page 18 EN MRM4 01 11 41 SG Prot ON 42 SG ON Cmd SG Prot ON SG ON Cmd...
Page 115: ...Navigation Operation Navigation Operation EN MRM4 01 11 Page 115 1 2 3 5 7 6 8 10 9...
Page 162: ...Recorder Name Description I 2 TripCmd Signal Trip Command Page 162 EN MRM4 01 11...