Measuring Values
Output 4..20mA*
Available Elements:
20 mA Output
This output is configured by the User to represent the status of User programmed parameters that are available
from the relay. The User will find the configuration menu for this feature under the [Device Para/20 mA Output]
menu option. Here the User can define to which parameter the 4-20 mA output will correlate.
Once the assignment has been made, the User can select the expected range of the parameter that will
correlate to the 4-20 mA output. The User will be required to enter a »
Range min«
, and »
Range max«
. The
»
Range min«
will determine the value at which 4 mA will be transmitted by the relay. Likewise, the »
Range
max«
value will determine the value that will result in the transmission of a 20 mA output.
*availability depends on ordered device.
Global Protection Parameters of the 4..20mA Output
Parameter
Description
Setting range
Default
Menu path
Assignment
Assignment
-,
I3 P (%Ib) avg,
I3P Fla Demand,
I2T Used,
I2T Remained,
Windg1,
Windg2,
Windg3,
Windg4,
Windg5,
Windg6,
MotBear1,
MotBear2,
LoadBear1,
LoadBear2,
Aux,
RTD Max,
Hot test Winding Temp
-
[Device Para
/20 mA Output]
Range min
Adjustable range
minimum
_ _ _ _ _ _ _ _ _ _ _ _ _
0 - 200
0
[Device Para
/20 mA Output]
Range max
Adjustable range
maximum
_ _ _ _ _ _ _ _ _ _ _ _ _
0 - 200
200
[Device Para
/20 mA Output]
Page 136
EN MRM4 01/11
Summary of Contents for MRM4
Page 1: ...MRM4 HighPROTEC Motor Protection Device Manual DOK HB MRM4E...
Page 3: ...Order Code EN MRM4 01 11 Page 3...
Page 18: ...Important Definitions Page 18 EN MRM4 01 11 41 SG Prot ON 42 SG ON Cmd SG Prot ON SG ON Cmd...
Page 115: ...Navigation Operation Navigation Operation EN MRM4 01 11 Page 115 1 2 3 5 7 6 8 10 9...
Page 162: ...Recorder Name Description I 2 TripCmd Signal Trip Command Page 162 EN MRM4 01 11...