Parameters
A star/parameter change indication is always overwritten by the question
mark/implausibility symbol.
If a device detects an implausibility, it rejects saving and adopting of the
parameters.
Changing of Parameters when using the Smart View - Example
Example: Changing of a protective parameter (to alter the characteristic for the overcurrent protection function
I[1] in parameter set 1).
In case
Smart View
is not in operation – start this software.
•
In case the device data has not been loaded – select »Data To Be Received From The Device« in menu
»Device«.
•
Double-click the »Protection Para Icon« in the navigation tree.
•
Double-click the »Protection Para Set Icon« in the navigation tree.
•
Double-click the »Set 1 Icon« in the navigation tree.
•
Double-click the »protection stage I[1]« in the navigation tree.
•
In the working window a tabulated overview appears, showing the parameters assigned to this protective
function.
•
In this table double-click the value/parameter you want to change (here:
»Char«
).
•
Another window (pop-up) is opened where you can select the required characteristic.
•
Close this window by clicking the »OK« key.
A star symbol in front of the changed parameters indicates that the
alterations have only temporarily been saved. They are not yet finally
stored and adopted by the software/device.
In order to make things easier to follow, especially where complex
parameter changes are involved, on every superior/higher menu level, the
intended change of the parameter is indicated by the star symbol (star
trace). This makes it possible to control or follow from the main menu level
at any time where parameter changes have been made and have not finally
been saved.
Plausibility check: In order to prevent obvious wrong settings the software
monitors constantly all temporarily saved parameter changes. If it detects
an implausibility, this is indicated by a question mark in front of the
respective parameter.
In order to make things easier to follow, especially where complex
parameter changes are involved, on every superior/higher menu level
above of the temporarily saved parameters, an implausibility is indicated by
Page 222
EN MRM4 01/11
Summary of Contents for MRM4
Page 1: ...MRM4 HighPROTEC Motor Protection Device Manual DOK HB MRM4E...
Page 3: ...Order Code EN MRM4 01 11 Page 3...
Page 18: ...Important Definitions Page 18 EN MRM4 01 11 41 SG Prot ON 42 SG ON Cmd SG Prot ON SG ON Cmd...
Page 115: ...Navigation Operation Navigation Operation EN MRM4 01 11 Page 115 1 2 3 5 7 6 8 10 9...
Page 162: ...Recorder Name Description I 2 TripCmd Signal Trip Command Page 162 EN MRM4 01 11...