Parameters
a question mark (plausibility trace). This makes it possible to control or
follow from the main menu level at any time where implausibilities exist.
So it is possible to see from each point of the menu tree that
implausibilities have been detected by the software.
A star/parameter change indication is always overwritten by the question
mark/implausibility symbol.
If the software detects an implausibility it rejects saving and adopting of the
parameters.
•
Additional parameters can be changed if required.
•
In order to transfer changed parameters into the device, please select »Transfer all parameters into the
device« in menu »Device«.
•
Confirm the safety inquiry »Shall The Parameters Be Overwritten?«.
•
Enter the password for setting parameters in the pop-up window.
•
Confirm the inquiry »Shall The Data Be Saved Locally?« with »Yes« (recommended). Select a suitable
storing location on your hard disk.
•
Confirm the chosen storing location by clicking »Save«.
•
The changed parameter data is now saved in the data file chosen by you. Thereafter the changed data
is transferred to the device and adopted.
Once you have entered the parameter setting password, Smart View wont
ask you again for the password for at least 10 minutes. This time interval
will start again, each time parameters are transmitted into the device. If for
more than 10 minutes no parameters are transmitted into the device, Smart
View will ask you again for the password, when you are trying to transmit
parameters into the device.
Protection Parameters
It has to be taken into account that by deactivating, for instance, protective
functions, you also change the functionality of the device.
The manufacturer does not accept liability for any personal or material
damage as a result of wrong planning.
A planning/parameter setting service is also offered by
Woodward Kempen
GmbH
.
The protection parameters include the following protection parameter trees.
•
Global Protection Parameters:
»Global Prot Para«
: Here you can find all protection parameters that are
universally valid, that means that they are valid independent of the protection parameter sets.
EN MRM4 01/11
Page 223
Summary of Contents for MRM4
Page 1: ...MRM4 HighPROTEC Motor Protection Device Manual DOK HB MRM4E...
Page 3: ...Order Code EN MRM4 01 11 Page 3...
Page 18: ...Important Definitions Page 18 EN MRM4 01 11 41 SG Prot ON 42 SG ON Cmd SG Prot ON SG ON Cmd...
Page 115: ...Navigation Operation Navigation Operation EN MRM4 01 11 Page 115 1 2 3 5 7 6 8 10 9...
Page 162: ...Recorder Name Description I 2 TripCmd Signal Trip Command Page 162 EN MRM4 01 11...