Protective Elements
Applications of the I-Protection Module
Setting in
Option
ANSI 51 – Short circuit protection, non-
directional
Device Planning menu
Measuring Mode:
Fundamental/TrueRMS/negative
phase sequence current (I2)
ANSI 51Q Negative Phase Sequence
Overcurrent Protection
(
Please refer to the 51Q chapter
)
Parameter Set: Measuring
Method =I2 (Negative
Sequence Current)
Measuring Mode
For all protection elements it can be determined, whether the measurement is done on basis of the
»
Fundamental«
or if »
TrueRMS«
measurement is used.
Alternatively the »
Measuring Mode«
can be set to
»I2«
. In this case the negative phase sequence current will be
measured. This is to detect unbalanced faults.
For each element the following characteristics are available:
•
DEFT (UMZ);
•
NINV (IEC/AMZ);
•
VINV (IEC/AMZ);
•
LINV (IEC/AMZ);
•
EINV (IEC/AMZ);
•
MINV (ANSI/AMZ);
•
VINV (ANSI/AMZ);
•
EINV (ANSI/AMZ);
•
Thermal Flat;
•
IT;
•
I2T; and
•
I4T.
Explanation:
By using the projecting parameters each of the overcurrent protective elements can be defined as
»forward«
,
»reverse«
or
»non-directional«
. The forward or reverse direction is based on the characteristic angle for the
phase direction specified by the field parameter
»I MTA«
. No directional information will be taken into account if
the current protective element is planned as
»non-directional«
EN MRM4 01/11
Page 289
t = Tripping delay
t-char = Time multiplier/tripping characteristic factor
I = Fault current
I> = If the pickup value is exceeded, the module/element starts to time out to trip.
Summary of Contents for MRM4
Page 1: ...MRM4 HighPROTEC Motor Protection Device Manual DOK HB MRM4E...
Page 3: ...Order Code EN MRM4 01 11 Page 3...
Page 18: ...Important Definitions Page 18 EN MRM4 01 11 41 SG Prot ON 42 SG ON Cmd SG Prot ON SG ON Cmd...
Page 115: ...Navigation Operation Navigation Operation EN MRM4 01 11 Page 115 1 2 3 5 7 6 8 10 9...
Page 162: ...Recorder Name Description I 2 TripCmd Signal Trip Command Page 162 EN MRM4 01 11...