Protective Elements
Parameter
Description
Setting range
Default
Menu path
I>
If the pickup value is
exceeded, the
module/element starts to
time out to trip.
Only available if:
Characteristic = DEFT
Or Characteristic = INV
Minimum of the setting
range If: VRestraint =
active Minimum of the
setting range If:
VRestraint = inactive.
0.02 - 40.00In
I[1]: 2.00In
1.00In
1.00In
1.00In
1.00In
I[2]: 5.00In
1.00In
1.00In
1.00In
1.00In
I[3]: 1.00In
I[4]: 1.00In
I[5]: 1.00In
I[6]: 1.00In
[Protection Para
/<n>
/I-Prot
/I[1]]
Char
Characteristic
DEFT,
IEC NINV,
IEC VINV,
IEC EINV,
IEC LINV,
ANSI MINV,
ANSI VINV,
ANSI EINV,
Therm Flat,
IT,
I2T,
I4T
DEFT
[Protection Para
/<n>
/I-Prot
/I[1]]
Page 306
EN MRM4 01/11