Input, Output and LED Settings
Input, Output and LED Settings
Configuration of the Digital Inputs
Based on the »assignment list«, the states of digital inputs are allocated to
the module inputs.
Set the following parameters for each of the digital inputs:
•
»Nominal voltage«;
•
»Debouncing time«
: A state change will only be adopted by the digital input after the debouncing time
has expired; and
•
»Inverting«
(where necessary).
The debouncing time will be started each time the state of the input signal
alternates.
In addition to the debouncing time that can be set via software, there is
always a hardware debouncing time (approx 12 ms) that cannot be turned
of.
DI-8P X
DI Slot X1
Device Parameters of the Digital Inputs on DI-8P X
Parameter
Description
Setting range
Default
Menu path
Nom voltage
Nominal voltage of the
digital inputs
24 V DC,
48 V DC,
60 V DC,
110 V DC,
230 V DC,
110 V AC,
230 V AC
24 V DC
[Device Para
/Digital Inputs
/DI Slot X1
/Group 1]
Page 58
EN MRM4 01/11
=1
State of the digital input
Inverting
Input Signal
Nom voltage
0
t
Debouncing time
DI Slot X.DI x