Trip and Breaker Management
Direct Commands of the CB Manager
Parameter
Description
Setting range
Default
Menu path
Ack TripCmd
Acknowledge Trip
Command
inactive,
active
inactive
[Operation
/Reset
/Flags]
Global Protection Parameters of the CB Manager
Parameter
Description
Setting range
Default
Menu path
t-TripCmd
Minimum hold time of the
OFF-command (circuit
breaker, load break
switch).
0.0 - 300.0s
0.2s
[Protection Para
/Global Prot Para
/CB Manager
/CB]
Latched
Defines whether the
Binary Output Relay will
be Latched when it picks
up.
inactive,
active
inactive
[Protection Para
/Global Prot Para
/CB Manager
/CB]
Ack TripCmd
Acknowledge Trip
Command
1..n, Assignment List
-.-
[Protection Para
/Global Prot Para
/CB Manager
/CB]
tmax-OFF
Within this time the OFF
command has to be
carried out by the CB.
Within this time the
position indicators (check
back signals) have to
change from ON to OFF.
0.00 - 10.00s
0.10s
[Protection Para
/Global Prot Para
/CB Manager
/CB]
tmax-ON
Within this time the ON
command has to be
carried out by the
Breaker. Within this time
the position indicators
(check back signals)
have to change from OFF
to ON.
0.00 - 10.00s
0.10s
[Protection Para
/Global Prot Para
/CB Manager
/CB]
Page 254
EN MRM4 01/11
Summary of Contents for MRM4
Page 1: ...MRM4 HighPROTEC Motor Protection Device Manual DOK HB MRM4E...
Page 3: ...Order Code EN MRM4 01 11 Page 3...
Page 18: ...Important Definitions Page 18 EN MRM4 01 11 41 SG Prot ON 42 SG ON Cmd SG Prot ON SG ON Cmd...
Page 115: ...Navigation Operation Navigation Operation EN MRM4 01 11 Page 115 1 2 3 5 7 6 8 10 9...
Page 162: ...Recorder Name Description I 2 TripCmd Signal Trip Command Page 162 EN MRM4 01 11...