Communication Protocols
Value
Description
Default
Size
Menu path
NoOfInternalError
Total Number of Internal
errors while interpreting
the request.
0
0 - 9999999999
[Operation
/Count and RevData
/Modbus]
Profibus
Profibus
Part 1: Configuration of the Devices
Call up
»Device parameter/Profibus«
and set the following communication parameter:
•
Slave-address, to allow clear identification of the device.
In addition to that the Master has to be provided with the GSD-file. The GSD-file can be taken from the Product-
CD.
Part 2: Hardware Connection
•
For hardware connection to the control system, there is optional an D-SUB interface at the rear side of
the device.
•
Connect bus and device (wiring).
•
Up to 123 slaves can be connected.
•
Terminate the Bus by means of an Terminate Resistor.
Error Handling
Information on physical communication errors, such as:
•
Baud Rate Error
can be obtained from the event recorder or the status display.
Error Handling – Status LED at the rear side
The Profibus D-SUB interface at the rear side of the device is equipped with a status LED.
•
Baud Search -> red flashing;
•
Baud Found -> green flashing;
•
Data Exchange -> green; and
•
No Profibus/Unplugged, not connected -> red.
EN MRM4 01/11
Page 193
Summary of Contents for MRM4
Page 1: ...MRM4 HighPROTEC Motor Protection Device Manual DOK HB MRM4E...
Page 3: ...Order Code EN MRM4 01 11 Page 3...
Page 18: ...Important Definitions Page 18 EN MRM4 01 11 41 SG Prot ON 42 SG ON Cmd SG Prot ON SG ON Cmd...
Page 115: ...Navigation Operation Navigation Operation EN MRM4 01 11 Page 115 1 2 3 5 7 6 8 10 9...
Page 162: ...Recorder Name Description I 2 TripCmd Signal Trip Command Page 162 EN MRM4 01 11...