Protective Elements
Name
Description
INSQSP2STFaill
Signal: Fail to transit from stop to start based on reported back
time
INSQSt2RunFail
Signal: Fail to transit from start to run based on reported back time
LATBlock
Signal: Long acceleration timer enforced
ColdStartSeq
Signal: Motor cold start sequence flag
ForcedStart
Signal: Motor being forced to start
TripPhaseReverse
Signal: Relay tripped because of phase reverse detection
EmergOverrideDI
Signal: Emergency override start blocking through digital input DI
EmergOverrideUI
Signal: Emergency override start blocking through front panel
ABSActive
Signal: Anti-backspin is active. For certain applications, such as
pumping a fluid up a pipe, the motor may be driven backward for a
period of time after it stops. The anti-backspin timer prevents
starting the motor while it is spinning in the reverse direction.
Blo-GOCStart
Signal: Ground Instantaneous Overcurrent Start Delay. GOC
(Instantaneous Overcurrent) elements are blocked for the time
programmed under this parameter.
Blo-IOCStart
Signal: Phase Instantaneous Overcurrent Start Delay. IOC
(Instantaneous Overcurrent) elements are blocked for the time
programmed under this parameter.
Blo-I<Start
Signal: Underload Start Delay. Underload(Instantaneous
Overcurrent) elements are blocked for the time programmed under
this parameter.
Blo-JamStart
Signal: JAM Start Delay. JAM(Instantaneous Overcurrent)
elements are blocked for the time programmed under this
parameter.
Blo-UnbalStart
Signal: Motor start block current unbalance signal.
Blo-Generic1
Generic Start Delay. This value can be used to block any
protective element. 1
Blo-Generic2
Generic Start Delay. This value can be used to block any
protective element. 2
Blo-Generic3
Generic Start Delay. This value can be used to block any
protective element. 3
Blo-Generic4
Generic Start Delay. This value can be used to block any
protective element. 4
Blo-Generic5
Generic Start Delay. This value can be used to block any
protective element. 5
I_Transit
Signal: Current transition signal
T_Transit
Signal: Time transition signal
StartMotorCmd
Signal: Start motor command
MotorStopBlo
Signal: Motor stop block other protection functions
EN MRM4 01/11
Page 283
Summary of Contents for MRM4
Page 1: ...MRM4 HighPROTEC Motor Protection Device Manual DOK HB MRM4E...
Page 3: ...Order Code EN MRM4 01 11 Page 3...
Page 18: ...Important Definitions Page 18 EN MRM4 01 11 41 SG Prot ON 42 SG ON Cmd SG Prot ON SG ON Cmd...
Page 115: ...Navigation Operation Navigation Operation EN MRM4 01 11 Page 115 1 2 3 5 7 6 8 10 9...
Page 162: ...Recorder Name Description I 2 TripCmd Signal Trip Command Page 162 EN MRM4 01 11...