Commissioning
Commissioning/Protection Test
Putting into operation/protection test must be carried out by authorized and
qualified personnel. Before the device is put into operation the related
documentation has to be read and understood.
With any test of the protection functions the following has to be checked:
•
Is activation/tripping saved in the event recorder?
•
Is tripping saved in the fault recorder?
•
Is tripping saved in the disturbance recorder?
•
Are all signals/messages correctly generated?
•
Do all general parametrized blocking functions work properly?
•
Do all temporary parametrized (via DI) blocking functions work
properly?
•
To enable checks on all LEDs and relay functions, these have to
be provided with the relevant alarm and tripping functions of the
respective protection functions/elements. This has to be tested in
practical operation.
Check of all temporary blockings (via digital inputs):
•
In order to avoid malfunctions, all blockings related to
tripping/non-tripping of protection function have to be tested.
The test can be very complex and should therefore be performed
by the same people who set up the protection concept.
Check of all general trip blockings:
•
All general trip blockings have to be tested.
Prior to the initial operation of the protection device all tripping times and
values shown in the adjustment list have to be confirmed by a secondary
test
Any description of functions, parameters, inputs, or outputs that do not
match the device in hand, can be ignored.
Putting out of Operation – Plug out the Relay
Warning! Dismounting the relay will lead to a loss of the protection
functionality. Ensure that there is a back-up protection. If you are not
aware of the consequences of dismounting the device – stop! Don´t start.
Inform SCADA before you start.
Switch-off the power supply.
Ensure, that the cabinet is dead and that there are no voltages that could
EN MRM4 01/11
Page 423
Summary of Contents for MRM4
Page 1: ...MRM4 HighPROTEC Motor Protection Device Manual DOK HB MRM4E...
Page 3: ...Order Code EN MRM4 01 11 Page 3...
Page 18: ...Important Definitions Page 18 EN MRM4 01 11 41 SG Prot ON 42 SG ON Cmd SG Prot ON SG ON Cmd...
Page 115: ...Navigation Operation Navigation Operation EN MRM4 01 11 Page 115 1 2 3 5 7 6 8 10 9...
Page 162: ...Recorder Name Description I 2 TripCmd Signal Trip Command Page 162 EN MRM4 01 11...