Trip and Breaker Management
Parameter
Description
Setting range
Default
Menu path
Manual ON
The circuit breaker was
switched on manually if
the state of the assigned
signal is true. This digital
input can be used by
some protective elements
(if they are available
within the device) like
Switch Onto Fault
(SOTF), e.g. as a trigger
signal.
-.-,
DI Slot X1.DI 1,
DI Slot X1.DI 2,
DI Slot X1.DI 3,
DI Slot X1.DI 4,
DI Slot X1.DI 1,
DI Slot X1.DI 2,
DI Slot X1.DI 3,
DI Slot X1.DI 4,
DI Slot X1.DI 5,
DI Slot X1.DI 6,
DI Slot X1.DI 7,
DI Slot X1.DI 8
-.-
[Protection Para
/Global Prot Para
/CB Manager
/CB]
Manual OFF
The circuit breaker was
switched off manually if
the state of the assigned
signal is true. This digital
input can be used by
some protective elements
(if they are available
within the device) like
Cold Load Pickup
(CLPU), e.g. as a trigger
signal.
-.-,
DI Slot X1.DI 1,
DI Slot X1.DI 2,
DI Slot X1.DI 3,
DI Slot X1.DI 4,
DI Slot X1.DI 1,
DI Slot X1.DI 2,
DI Slot X1.DI 3,
DI Slot X1.DI 4,
DI Slot X1.DI 5,
DI Slot X1.DI 6,
DI Slot X1.DI 7,
DI Slot X1.DI 8
-.-
[Protection Para
/Global Prot Para
/CB Manager
/CB]
Page 256
EN MRM4 01/11
Summary of Contents for MRM4
Page 1: ...MRM4 HighPROTEC Motor Protection Device Manual DOK HB MRM4E...
Page 3: ...Order Code EN MRM4 01 11 Page 3...
Page 18: ...Important Definitions Page 18 EN MRM4 01 11 41 SG Prot ON 42 SG ON Cmd SG Prot ON SG ON Cmd...
Page 115: ...Navigation Operation Navigation Operation EN MRM4 01 11 Page 115 1 2 3 5 7 6 8 10 9...
Page 162: ...Recorder Name Description I 2 TripCmd Signal Trip Command Page 162 EN MRM4 01 11...