Smart View
Set-up a Connection via Ethernet - TCP/IP
Warning: Mixing up IP-Addresses (In case that there is more than one
protective device within the TCP/IP network). Establishing an unintentional
wrong connection to a protective device based on a wrong entered IP-
Address. Transferring parameters into a wrong protective device might
lead to death, personal injury or damage of electrical equipment.
In order to prevent faulty connections the user has to document and
maintain a list with the IP addresses of any switchboard/protective device.
The user has to double check the IP addresses of the connection that is to
be established. That means, the user must first read out the IP address at
the HMI of the device (within menu [Device para/TCP IP] then compare the
IP address with the list. If the addresses are identical, establish the
connection. If not, DO not connect.
Establishing a connection via TCP/IP to the device is only possible if your
device is equipped with an Ethernet Interface (RJ45).
Contact your IT administrator in order to establish the network connection.
Part 1: Set the TCP/IP Parameters at the panel (Device)
Call up the menu
»Device parameter/TCP/IP«
at the HMI (panel) and set the following parameters:
•
TCP/IP address;
•
Subnet mask; and
•
Gateway.
Part 2: Setting the IP address within Smart View
•
Call up the menu Settings/Device Connection within Smart View.
•
Set radio button Network Connection.
•
Enter the IP-Address of the device that should be connected.
Smart View Troubleshooting (XP and Windows 2000)
•
Make sure whether the Windows service
Telephony
is started. In [Start>System Control >Administration
>Services] the service »Telephony« must be visible and must have also been started. If not, the service
has to be started.
•
•
For establishing the connection, you need to have sufficient rights (administration rights).
•
If a firewall is installed on your computer, TCP/IP port 52152 must have been released.
•
If your computer is not provided with a serial interface, you need a
USB-to-serial-adapter
, accepted by
Woodward Kempen GmbH
. This adapter has to be properly installed.
EN MRM4 01/11
Page 127
Summary of Contents for MRM4
Page 1: ...MRM4 HighPROTEC Motor Protection Device Manual DOK HB MRM4E...
Page 3: ...Order Code EN MRM4 01 11 Page 3...
Page 18: ...Important Definitions Page 18 EN MRM4 01 11 41 SG Prot ON 42 SG ON Cmd SG Prot ON SG ON Cmd...
Page 115: ...Navigation Operation Navigation Operation EN MRM4 01 11 Page 115 1 2 3 5 7 6 8 10 9...
Page 162: ...Recorder Name Description I 2 TripCmd Signal Trip Command Page 162 EN MRM4 01 11...