Device Parameters
Set the TCP/IP Parameters
Call up
»Device parameter/TCP/IP«
at the HMI (panel) and set the following parameters:
•
TCP/IP address;
•
•
Subnetmask; and
•
Gateway.
Direct Commands of the System Module
Parameter
Description
Setting range
Default
Menu path
Ack BO LED Scd TCmd
Reset the binary output
relays, LEDs, SCADA
and the Trip Command.
inactive,
active
inactive
[Operation
/Reset
/Flags]
Ack LED
All acknowledgeable
LEDs will be
acknowledged.
inactive,
active
inactive
[Operation
/Reset
/Flags]
Ack BO
All acknowledgeable
binary output relays will
be acknowledged.
inactive,
active
inactive
[Operation
/Reset
/Flags]
Ack Scada
SCADA will be
acknowledged.
inactive,
active
inactive
[Operation
/Reset
/Flags]
Res OperationsCr
Reset all counters in
history group operations
inactive,
active
inactive
[Operation
/Reset
/History]
Res AlarmCr
Reset all counters in
history group alarms
inactive,
active
inactive
[Operation
/Reset
/History]
Res TripCr
Reset all counters in
history group trips
inactive,
active
inactive
[Operation
/Reset
/History]
Res TotalCr
Reset all counters in
history group total
inactive,
active
inactive
[Operation
/Reset
/History]
Res All
Reset of all Counters
inactive,
active
inactive
[Operation
/Reset
/History]
Reboot
Rebooting the device.
no,
yes
no
[Service
/General]
Page 228
EN MRM4 01/11
Summary of Contents for MRM4
Page 1: ...MRM4 HighPROTEC Motor Protection Device Manual DOK HB MRM4E...
Page 3: ...Order Code EN MRM4 01 11 Page 3...
Page 18: ...Important Definitions Page 18 EN MRM4 01 11 41 SG Prot ON 42 SG ON Cmd SG Prot ON SG ON Cmd...
Page 115: ...Navigation Operation Navigation Operation EN MRM4 01 11 Page 115 1 2 3 5 7 6 8 10 9...
Page 162: ...Recorder Name Description I 2 TripCmd Signal Trip Command Page 162 EN MRM4 01 11...