Protective Elements
Parameter
Description
Setting range
Default
Menu path
ZSS
Zero Speed Switch
Only available if: ZSS =
active
-.-,
DI Slot X1.DI 1,
DI Slot X1.DI 2,
DI Slot X1.DI 3,
DI Slot X1.DI 4,
DI Slot X1.DI 1,
DI Slot X1.DI 2,
DI Slot X1.DI 3,
DI Slot X1.DI 4,
DI Slot X1.DI 5,
DI Slot X1.DI 6,
DI Slot X1.DI 7,
DI Slot X1.DI 8
-.-
[Protection Para
/Global Prot Para
/MStart
/Motor Inputs]
t-Blo-IOC
Phase Overcurrent Start
Delay. Phase
Overcurrent elements are
blocked for the time
programmed under this
parameter, while the
motor is starting.
0.03 - 1.00s
0.05s
[Protection Para
/Global Prot Para
/MStart
/Start Delay Timer]
t-Blo-GOC
Ground Overcurrent Start
Delay. Ground
Overcurrent elements are
blocked for the time
programmed under this
parameter, while the
motor is starting.
0.03 - 1.00s
0.08s
[Protection Para
/Global Prot Para
/MStart
/Start Delay Timer]
t-Blo-I<
Underload Start Delay.
37[x] elements are
blocked for the time
programmed under this
parameter, while the
motor is starting.
0 - 1200s
60s
[Protection Para
/Global Prot Para
/MStart
/Start Delay Timer]
t-Blo-IUnbalance
Current Unbalance Start
Delay. 46[x] elements
are blocked for the time
programmed under this
parameter, while the
motor is starting.
0 - 1200s
10s
[Protection Para
/Global Prot Para
/MStart
/Start Delay Timer]
t-Blo-JAM
Jam Start Delay. 50J[x]
elements are blocked for
the time programmed
under this parameter,
while the motor is
starting.
0 - 1200s
60s
[Protection Para
/Global Prot Para
/MStart
/Start Delay Timer]
Page 280
EN MRM4 01/11
Summary of Contents for MRM4
Page 1: ...MRM4 HighPROTEC Motor Protection Device Manual DOK HB MRM4E...
Page 3: ...Order Code EN MRM4 01 11 Page 3...
Page 18: ...Important Definitions Page 18 EN MRM4 01 11 41 SG Prot ON 42 SG ON Cmd SG Prot ON SG ON Cmd...
Page 115: ...Navigation Operation Navigation Operation EN MRM4 01 11 Page 115 1 2 3 5 7 6 8 10 9...
Page 162: ...Recorder Name Description I 2 TripCmd Signal Trip Command Page 162 EN MRM4 01 11...