Device Parameters
CAUTION, rebooting the device manually will release the Supervision
Contact.
Global Protection Parameters of the System
Parameter
Description
Setting range
Default
Menu path
PSet-Switch
Switching Parameter Set PS1,
PS2,
PS3,
PS4,
PSS via Inp fct,
PSS via Scada
PSS via Inp fct
[Protection Para
/PSet-Switch]
PS1: activated by
This Setting Group will be
the active one if: The
Parameter Setting Group
Switch is set to "Switch
via Input" and the other
three input functions are
inactive at the same time.
In case that there is more
than one input function
active, no Parameter
Setting Group Switch will
be executed. In case all
input functions are
inactive, the device will
keep working with the
Setting Group that was
activated lastly.
Only available if: PSet-
Switch = PSS via Inp
fct.
-.-,
DI Slot X1.DI 1,
DI Slot X1.DI 2,
DI Slot X1.DI 3,
DI Slot X1.DI 4,
DI Slot X1.DI 1,
DI Slot X1.DI 2,
DI Slot X1.DI 3,
DI Slot X1.DI 4,
DI Slot X1.DI 5,
DI Slot X1.DI 6,
DI Slot X1.DI 7,
DI Slot X1.DI 8
-.-
[Protection Para
/PSet-Switch]