Protective Elements
Parameter
Description
Setting range
Default
Menu path
LoadBear 1 t-Delay
Load Bearing 1 If this
time is expired a
Temperature Alarm will
be generated.
Only available if: Device
planning: Alarm Function
= use.
0 - 360min
1min
[Protection Para
/<n>
/Temp-Prot
/RTD
/LoadBear 1]
LoadBear 1 Trip
Load Bearing 1
Threshold for
Temperature Trip
Only available if: Device
planning: Trip Function =
use.
0 - 200°C
80°C
[Protection Para
/<n>
/Temp-Prot
/RTD
/LoadBear 1]
LoadBear 2 Alarm
Function
Load Bearing 2 Alarm
Function
inactive,
active
active
[Protection Para
/<n>
/Temp-Prot
/RTD
/LoadBear 2]
LoadBear 2 LoadBear
Load Bearing 2 Trip
Function
inactive,
active
active
[Protection Para
/<n>
/Temp-Prot
/RTD
/LoadBear 2]
LoadBear 2 Alarm
Load Bearing 2
Threshold for
Temperature Alarm
Only available if: Device
planning: Alarm Function
= use.
0 - 200°C
80°C
[Protection Para
/<n>
/Temp-Prot
/RTD
/LoadBear 2]
LoadBear 2 t-Delay
Load Bearing 2 If this
time is expired a
Temperature Alarm will
be generated.
Only available if: Device
planning: Alarm Function
= use.
0 - 360min
1min
[Protection Para
/<n>
/Temp-Prot
/RTD
/LoadBear 2]
LoadBear 2 Trip
Load Bearing 2
Threshold for
Temperature Trip
Only available if: Device
planning: Trip Function =
use.
0 - 200°C
80°C
[Protection Para
/<n>
/Temp-Prot
/RTD
/LoadBear 2]
Page 370
EN MRM4 01/11
Summary of Contents for MRM4
Page 1: ...MRM4 HighPROTEC Motor Protection Device Manual DOK HB MRM4E...
Page 3: ...Order Code EN MRM4 01 11 Page 3...
Page 18: ...Important Definitions Page 18 EN MRM4 01 11 41 SG Prot ON 42 SG ON Cmd SG Prot ON SG ON Cmd...
Page 115: ...Navigation Operation Navigation Operation EN MRM4 01 11 Page 115 1 2 3 5 7 6 8 10 9...
Page 162: ...Recorder Name Description I 2 TripCmd Signal Trip Command Page 162 EN MRM4 01 11...