Communication Protocols
Part 1: Setting the TCP/IP Parameters
Call up
»Device parameter/TCP/IP«
at the HMI (panel) and set the following parameters:
•
TCP/IP address;
•
Subnetmask; and
•
Gateway.
Part 2: Configuration of the Devices
Call up
»Device parameter/Modbus«
and set the following communication parameters.
•
Setting a Unit Identifier is only necessary if a TCP network should be coupled to a RTU network.
•
If a different port than the default port 502 should be used please proceed as follows:
•
Choose “Private” within the TCP-Port-Configuration; and
•
Set the port-number.
•
Set the maximum accepted time of “no communication”. If this time has expired – without any
communication, the device concludes a failure within the master system.
•
Allow or disallow the blocking of SCADA commands.
Part 3: Hardware Connection
•
There is a RJ45 interface at the rear side of the device for the hardware connection to the control
system.
•
Establish the connection to the device by means of a proper Ethernet cable.
Direct Commands of the Modbus
®
Parameter
Description
Setting range
Default
Menu path
Res Diagn Cr
All Modbus Diagnosis
Counters will be reset.
inactive,
active
inactive
[Operation
/Reset
/Counter]
Page 188
EN MRM4 01/11
Summary of Contents for MRM4
Page 1: ...MRM4 HighPROTEC Motor Protection Device Manual DOK HB MRM4E...
Page 3: ...Order Code EN MRM4 01 11 Page 3...
Page 18: ...Important Definitions Page 18 EN MRM4 01 11 41 SG Prot ON 42 SG ON Cmd SG Prot ON SG ON Cmd...
Page 115: ...Navigation Operation Navigation Operation EN MRM4 01 11 Page 115 1 2 3 5 7 6 8 10 9...
Page 162: ...Recorder Name Description I 2 TripCmd Signal Trip Command Page 162 EN MRM4 01 11...