Assignment List
Name
Description
BW.ExBlo
Signal: External Blocking
BW.Operations Alarm
Signal: Service Alarm, too many Operations
BW.Isum Intr trip: IL1
Signal: Maximum permissible Summation of the interrupting
(tripping) currents exceeded: IL1
BW.Isum Intr trip: IL2
Signal: Maximum permissible Summation of the interrupting
(tripping) currents exceeded: IL2
BW.Isum Intr trip: IL3
Signal: Maximum permissible Summation of the interrupting
(tripping) currents exceeded: IL3
BW.Isum Intr trip
Signal: Maximum permissible Summation of the interrupting
(tripping) currents exceeded in at least one phase.
BW.Res TripCmd Cr
Signal: Resetting of the Counter: total number of trip commands
BW.Res Sum trip
Signal: Reset summation of the tripping currents
BW.ExBlo1-I
Module input state: External blocking1
BW.ExBlo2-I
Module input state: External blocking2
MStart.active
Signal: active
MStart.Blo TripCmd
Signal: Trip Command blocked
MStart.Trip
Signal: Trip
MStart.TripCmd
Signal: Trip Command
MStart.Start
Signal: Motor is in start mode
MStart.Run
Signal: Motor is in run mode
MStart.Stop
Signal: Motor is in stop mode
MStart.Blo
Signal: Motor is blocked for starting or transition to Run mode
MStart.NOCSBlocked
Signal: Motor is prohibited to start due to number of cold start
limits
MStart.SPHBlocked
Signal: Motor is prohibited to start due to starts per hour limits
MStart.SPHBlockAlarm
Signal: Motor is prohibited to start due to starts per hour limits,
would come active in the next stop
MStart.TBSBlocked
Signal: Motor is prohibited to start due to time between starts limits
MStart.ThermalBlo
Signal: Thermal block
MStart.RemBlockStart
Signal: Motor is prohibited to start due to external blocking through
digital input DI
MStart.TransitionTrip
Signal: Start transition fail trip
MStart.ZSSTrip
Signal: Zero speed trip (possible locked rotor)
MStart.INSQSP2STFaill
Signal: Fail to transit from stop to start based on reported back
time
MStart.INSQSt2RunFail
Signal: Fail to transit from start to run based on reported back time
MStart.LATBlock
Signal: Long acceleration timer enforced
MStart.ColdStartSeq
Signal: Motor cold start sequence flag
MStart.ForcedStart
Signal: Motor being forced to start
MStart.TripPhaseReverse
Signal: Relay tripped because of phase reverse detection
MStart.EmergOverrideDI
Signal: Emergency override start blocking through digital input DI
MStart.EmergOverrideUI
Signal: Emergency override start blocking through front panel
Page 440
EN MRM4 01/11
Summary of Contents for MRM4
Page 1: ...MRM4 HighPROTEC Motor Protection Device Manual DOK HB MRM4E...
Page 3: ...Order Code EN MRM4 01 11 Page 3...
Page 18: ...Important Definitions Page 18 EN MRM4 01 11 41 SG Prot ON 42 SG ON Cmd SG Prot ON SG ON Cmd...
Page 115: ...Navigation Operation Navigation Operation EN MRM4 01 11 Page 115 1 2 3 5 7 6 8 10 9...
Page 162: ...Recorder Name Description I 2 TripCmd Signal Trip Command Page 162 EN MRM4 01 11...