Recorder
•
If device data has not been loaded yet – click »Receive Data From The Device« in menu »Device«.
•
Double click the »Operation« icon in the navigation tree.
•
Double click the »Recorders« icon in the navigation tree.
•
Double click the »Disturb rec-Icon«.
•
In the window the disturbance records are shown in tabular form.
•
In order to delete a disturbance record double click on:
(the red x) in front of the disturbance record and confirm.
Direct Commands of the Disturbance Recorder
Parameter
Description
Setting range
Default
Menu path
Man Trigger
Manual Trigger
False,
True
False
[Operation
/Recorders
/Man Trigger]
Res all rec
Reset all records
inactive,
active
inactive
[Operation
/Reset
/Flags]
Global Protection Parameters of the Disturbance Recorder
Parameter
Description
Setting range
Default
Menu path
Start: 1
Start recording if the
assigned signal is true.
1..n, Assignment List
Prot.Alarm
[Device Para
/Recorders
/Disturb rec]
Start: 2
Start recording if the
assigned signal is true.
1..n, Assignment List
-.-
[Device Para
/Recorders
/Disturb rec]
Start: 3
Start recording if the
assigned signal is true.
1..n, Assignment List
-.-
[Device Para
/Recorders
/Disturb rec]
Start: 4
Start recording if the
assigned signal is true.
1..n, Assignment List
-.-
[Device Para
/Recorders
/Disturb rec]
Start: 5
Start recording if the
assigned signal is true.
1..n, Assignment List
-.-
[Device Para
/Recorders
/Disturb rec]
Page 156
EN MRM4 01/11
Summary of Contents for MRM4
Page 1: ...MRM4 HighPROTEC Motor Protection Device Manual DOK HB MRM4E...
Page 3: ...Order Code EN MRM4 01 11 Page 3...
Page 18: ...Important Definitions Page 18 EN MRM4 01 11 41 SG Prot ON 42 SG ON Cmd SG Prot ON SG ON Cmd...
Page 115: ...Navigation Operation Navigation Operation EN MRM4 01 11 Page 115 1 2 3 5 7 6 8 10 9...
Page 162: ...Recorder Name Description I 2 TripCmd Signal Trip Command Page 162 EN MRM4 01 11...