Protective Elements
Motor Protection Curves
Motor Protection Curve (Example 1)
Page 394
EN MRM4 01/11
Ultimate trip
based on % of
full-load
amperes
(100% shown)
I
2
T Curves
(I is an effective
current including
I
1
and kI
2
)
Maximum allowable
stall time
(30 Sec. cold start)
(15 Sec. cold start)
(10 Sec. cold start)
( 5 Sec. cold start)
Based upon locked
rotor current of 6.1
times full-load amps
Instantaneous
overcurrent set at
12 times full-load
amperes
Instantaneous
overcurrent start
delay set for
2 cycles
multiples of Ib
t [s
]