Protective Elements
Parameter
Description
Setting range
Default
Menu path
ExBlo Fc
Activate (allow) or
inactivate (disallow)
blocking of the
module/stage. This
parameter is only
effective if a signal is
assigned to the
corresponding global
protection parameter. If
the signal becomes true,
those modules/stages
are blocked that are
parametrized "ExBlo
Fc=active".
inactive,
active
inactive
[Protection Para
/<n>
/I-Prot
/I2>[1]]
Blo TripCmd
Permanent blocking of
the Trip Command of the
module/stage.
inactive,
active
inactive
[Protection Para
/<n>
/I-Prot
/I2>[1]]
ExBlo TripCmd Fc
Activate (allow) or
inactivate (disallow)
blocking of the
module/stage. This
parameter is only
effective if a signal is
assigned to the
corresponding global
protection parameter. If
the signal becomes true,
those modules/stages
are blocked that are
parametrized "ExBlo
TripCmd Fc=active".
inactive,
active
inactive
[Protection Para
/<n>
/I-Prot
/I2>[1]]
I2>
The Threshold setting
defines a minimum
operating current
magnitude of I2 for the 46
function to operate, which
ensures that the relay
has a solid basis for
initiating a current
unbalance trip. This is a
supervisory function and
not a trip level.
0.01 - 4.00In
0.01In
[Protection Para
/<n>
/I-Prot
/I2>[1]]
%(I2/I1)
The %(I2/I1) setting is the
unbalance trip pickup
setting. It is defined by
the ratio of negative
sequence current to
positive sequence current
(% Unbalance=I2/I1), or
%(I2/I1) for ABC rotation
and %(I1/I2) for ACB
rotation.
inactive,
active
inactive
[Protection Para
/<n>
/I-Prot
/I2>[1]]
EN MRM4 01/11
Page 317
Summary of Contents for MRM4
Page 1: ...MRM4 HighPROTEC Motor Protection Device Manual DOK HB MRM4E...
Page 3: ...Order Code EN MRM4 01 11 Page 3...
Page 18: ...Important Definitions Page 18 EN MRM4 01 11 41 SG Prot ON 42 SG ON Cmd SG Prot ON SG ON Cmd...
Page 115: ...Navigation Operation Navigation Operation EN MRM4 01 11 Page 115 1 2 3 5 7 6 8 10 9...
Page 162: ...Recorder Name Description I 2 TripCmd Signal Trip Command Page 162 EN MRM4 01 11...