background image

QUICK START GUIDE 

FOR 

BE1-11 

Protection Systems 

 

 

 

 

Publication:  9424200772 

 

Revision:  D 

May-17 

 

Summary of Contents for BE1-11f

Page 1: ...QUICK START GUIDE FOR BE1 11 Protection Systems Publication 9424200772 Revision D May 17 ...

Page 2: ......

Page 3: ...enerator Protection System Publication 9424200994 BE1 11i Intertie Protection System Publication 9424200993 BE1 11m Motor Protection System Publication 9424200996 BE1 11t Transformer Protection System Publication 9424200995 Conventions Used in this Manual Important safety and procedural information is emphasized and presented in this manual through warning caution and note boxes Each type is illus...

Page 4: ...ion operation or maintenance For terms of service relating to this product and software see the Commercial Terms of Products and Services document available at www basler com terms This publication contains confidential information of Basler Electric Company an Illinois corporation It is loaned for confidential use subject to return on request and with the mutual understanding that it will not be ...

Page 5: ...age 1 Install BESTCOMSPlus Software 1 Power Up and Activate the BE1 11 Plug In 2 USB Connection 2 Apply Operating Power 2 Start BESTCOMSPlus and Activate BE1 11 Plugin 4 Programming the BE1 11 6 Introduction to BESTCOMSPlus 6 Summary Screens 7 Programming Example 8 Revision History 15 ...

Page 6: ...iv 9424200772 Rev D Contents BE1 11 ...

Page 7: ...aintenance consists of periodic replacement of the backup battery and periodically checking that the connections between the BE1 11 and the system are clean and tight The front cover should be removed only when replacing the backup battery for the real time clock Ensure that the BE1 11 is powered off and taken out of service before removing the front cover BE1 11 units are manufactured using state...

Page 8: ... and Activate the BE1 11 Plug In The BE1 11 plugin is a module that runs inside the BESTCOMSPlus shell The BE1 11 plugin contains specific operational and logic settings for only BE1 11 protection systems Uploading settings to the BE1 11 is possible only after activating the BE1 11 plugin Note that if a BE1 11 is not connected you will not be able to configure certain Ethernet settings Ethernet se...

Page 9: ...ominal power supply values listed on the front panel label Wait until the boot sequence is complete Figure 2 PWR Rear Terminals J Type Case with Standard I O Option ETHERNET WARNING BE1 11 C12 C11 C10 C9 C8 C7 C6 C5 C4 C3 C2 C1 C13 C14 C15 C16 C17 C18 VA OUT 2 OUT 3 OUT 4 OUT 5 OUT 1 ALARM VB VC V X VX N E12 E11 E10 E9 E8 E7 E6 E5 E4 E3 E2 E1 OUT 8 OUT 7 IN5 IN6 IN7 OUT 6 A8 A7 A6 A5 A4 A3 A2 A1 I...

Page 10: ...e BESTCOMSPlus Select Language screen is displayed Figure 4 You can choose to have this screen displayed each time BESTCOMSPlus is started or you can select a preferred language and this screen will be bypassed in the future Click OK to continue This screen can be accessed later by selecting Tools and Select Language from the menu bar Figure 4 BESTCOMSPlus Select Language Screen The BESTCOMSPlus s...

Page 11: ...t BE1 11 See Figure 6 The BE1 11 plugin is activated automatically after connecting to a BE1 11 Figure 6 Communication Pull Down Menu The BE1 11 Connection screen shown in Figure 7 appears Select USB Connection and then click the Connect button The BE1 11 plugin opens indicating that activation was successful You can now configure the BE1 11 communication ports and other BE1 11 settings ...

Page 12: ...created saved as a file and then uploaded to the BE1 11 at the user s convenience The BE1 11 plugin opens inside the BESTCOMSPlus main shell The same default logic scheme that is shipped with the BE1 11 is brought into BESTCOMSPlus by downloading settings and logic from the BE1 11 or by selecting application type F I G T or M on the Style Number screen This gives the user the option of developing ...

Page 13: ...he lower right hand corner provides interpretation for the various indicated colors The current state of a protection and control function or element is indicated by the color of the adjacent indicator If the function is enabled the color is green If the function is disabled only by a setting such as zero the color is yellow If the function is disabled only by a mode the color is blue If the funct...

Page 14: ... Figure 6 Step 2 The BE1 11 Connection screen appears See Figure 7 Select USB Connection and click Connect Step 3 Select Download Settings and Logic from Device from the Communication pull down menu This copies all settings and logic from the BE1 11 to BESTCOMSPlus Step 4 Click on the View drop down button and de select Show Metering Panel and Show Setting Information See Figure 9 This maximizes t...

Page 15: ...uts are used to make connections between logic pages and help keep logic diagrams free from clutter The Trip output is connected to an Off Page Output named 50 3 Trip This 50 3 Trip Off Page Output is carried over to Logic Page 2 Figure 14 where it becomes an Off Page Input The 50 3 Trip Off Page Input and several others are AND gated to the Trip Bus Off Page Output which is carried over to Logic ...

Page 16: ...10 9424200772 Rev D Quick Start Guide BE1 11 Figure 13 BESTlogicPlus Logic Page 1 Figure 14 BESTlogicPlus Logic Page 2 ...

Page 17: ... of the 50 3 element and drag it to the input of OUT4 to make a connection Refer to Figure 16 Figure 16 BESTlogicPlus Programming OUT4 Step 11 In this step the Pickup output of the 50 3 element is connected to User Alarm 1 When the Pickup output of the 50 3 element is true the label of the user alarm is displayed on the Alarms screen on the front panel display and in the fault report and or sequen...

Page 18: ...n in the settings file See Figure 18 Figure 18 BESTlogicPlus Toolbar Step 13 In the Settings Explorer expand Programmable Outputs Contact Outputs and name Output 4 50 3 Pickup as shown in Figure 19 Step 14 In the Settings Explorer expand Alarm Configuration User Programmable Alarms and name User Programmable Alarm 1 50 3 Pickup as shown in Figure 20 Figure 19 Contact Outputs Screen ...

Page 19: ...USERALM1 that were named in Step 13 and Step 14 Step 16 Select Save from the File pull down menu to save your new settings file Step 17 To make your new settings active in the BE1 11 select Upload Settings and Logic to Device from the Communication pull down menu Enter the username and password Figure 21 OUT4 and USERALM1 with User Defined Labels ...

Page 20: ...14 9424200772 Rev D Quick Start Guide BE1 11 ...

Page 21: ...Guide Revision and Date Change A Apr 14 Initial release consolidated 9424200893 9424200894 9424200895 9424200896 and 9424200998 B Dec 15 Updated Figure 12 to show Primary A pickup setting C Jul 16 Added Windows 10 compatibility for BESTCOMSPlus software Replaced Figures 4 and 6 to keep consistent with BESTCOMSPlus version 3 14 00 Added a note about standard I O option in the paragraph above Figure...

Page 22: ...16 9424200772 Rev D Revision History BE1 11 ...

Page 23: ......

Page 24: ... basler com No 59 Heshun Road Loufeng District N Suzhou Industrial Park 215122 Suzhou P R CHINA Tel 86 512 8227 2888 Fax 86 512 8227 2887 email chinainfo basler com 111 North Bridge Road 15 06 Peninsula Plaza Singapore 179098 Tel 65 68 44 6445 Fax 65 68 44 8902 email singaporeinfo basler com ...

Reviews: