Chapter 5 - Features and Components
_______________________________________________________________________________________________________________
MNL000626.doc
Revision 0
06/25/2019
Chemical Equipment
© Versum Materials US, LLC. as of the revision and date shown. All rights reserved.
Confidential and Proprietary Data
Page 5
-
16
Versum Materials Confidential
Sniffer port location
5.3.4 High Temperature Detection Switch (optional)
A temperature switch mounted on the exhaust sensor assembly will alarm if temperature
inside the ChemGuard® cabinet rises above 45-52°C. A High Temp alarm will be generated
and will terminate all operations and return the cabinet to IDEL state. Refer to Chapter 7 for
testing of the sensor.
5.3.5 Fire Suppression System (optional)
The Fire Suppression System is an independent system, equipped with a rate of rise
detection sensor. The sensor will trigger an alarm if a rise of temperature in the cabinet
exceeds 40°C in a period of less than one (1) minute. The Fire Suppression System will then