Chapter 3 - Installation
_______________________________________________________________________________________________________________
MNL000624.doc
Revision 0
06/25/2019
Chemical Equipment
© Versum Materials US, LLC. as of the revision and date shown. All rights reserved.
Confidential and Proprietary Data
Page 3
-
28
Versum Materials Confidential
Figure 3-12: Alarm and Controller Status Box
3.9.8
Screen Saver
When the programmed amount of time has elapsed since the operator’s last keypad
action, the screen saver blanks the display screen and a randomly-moving mode indicator
box appears. This occurs during the following states: idle, Chem On and External Fill (in
systems with a Bulk refill option.)
The screen saver will de-activate if a new alarm appears.
To manually de-activate the screen saver, touch anywhere on the display screen.
The screen saver function will not be active while a fault or shutdown alarm is present, an
active prompt is displayed, or during any mode/sequence other than idle and Chem On
(Chem On or External Fill, if Bulk refill option is available).
3.10 System Configuration
3.10.1
User Setpoints
– Bulk Scale (Analog)
Configuring Bulk analog scale External Fill & alarm setpoints
From the Main Menu, enter Config Menu -> User Setpoints -> Bulk Scale. Note, values
shown are recommended
Table 3-14: User Setpoints > Bulk Scale
Num
Alarm Label
Percent
1
BULK RES OVERFULL
85%
2
BULK RES LOW
15%
3
BULK RES EMPTY
10%
4
BUBLR STOP LEVEL
70%
5
BUBLR START LEVEL
68%